Hybrid inverter · Neovolt · CEC approved November 2026
Neovolt BW-INV-SPH5K
CEC listing: BW-INV-SPH5K (AS4777-2 2020)
A 5 kW single-phase hybrid inverter that is battery-ready and listed for battery storage on Synergy's list.
- Listed for battery storage on Synergy's list
- Yes
- Rated power
- 5kW
- How much solar it can run at once
- Battery-ready
- Yes
- A battery plugs straight in
- Feed-in credits (DEBS)
- Yes
- DEBS pays for exports only when the inverter is 5 kW or less
Listed for battery storage on Synergy's list: Synergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.
Key specs, in plain terms
The numbers that matter for a home. The full datasheet is below.
- Rated power
- 5kW
- How much solar it can turn into usable power at once
- Max efficiency
- 97.0%
- How much of the solar you make reaches the house
- Phases
- Single
- Runs on a standard single-phase supply
- Type
- Hybrid
- Runs solar and a battery from one unit
- Warranty
- 10yr
- How long Bytewatt Technology Co Ltd stands behind it
What we can tell you
Read from the figures on this page. No review written yet.
- It is a hybrid inverter: solar and a battery run from the one unit, so adding a battery later doesn't need a second box.
- It runs on a standard single-phase supply.
- Listed for battery storage on Synergy's list. Synergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.
- It is CEC-approved, which a new install needs to qualify for STCs.
Features and CEC approval
- Battery compatible
- Yes
- Backup capable
- Yes
- CEC approved
- 18 Nov 2026
- Approval expiry
- 17 Mar 2028
- Status
- Active
- Listed for STCs
- Yes
About Neovolt
- Years on the CEC list
- 3 years
- Australian office
- Not verified
- Category
- Budget
- CEC-approved inverters
- 21
- CEC-approved batteries
- 14
Documents
WA compliance
- Listed for battery storage on Synergy's list
- Yes
- Remote management
- On Synergy's list
Listed for battery storage on Synergy's list. Synergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.Western Power approval is required for every grid-connected install. Under Emergency Solar Management, a new system must be remotely manageable, or take an export limit instead. On Synergy's list dated 6 November 2026, this model is approved for remote management (CSIP-AUS).
Perth performance
Estimate for a full-size array on this inverter
- Daily yield
- 21.3 kWh
- Annual yield
- 7,756 kWh
At 5 peak sun hours a day (BOM) with a 15% system derate.
Get a quote from an installer sourced from the WA (Synergy/Plenti) approved list
Full datasheet
Every figure on file for the Neovolt BW-INV-SPH5K, by section.
| Specification | Value |
|---|---|
| Power & output | |
| Nominal power | 5 kW |
| Efficiency | |
| Max efficiency | 97% |
| Physical | |
| Dimensions (H×W×D) | 405 × 590 × 205 mm |
| Weight | 19.5 kg |
| IP rating | IP65 |
| Rebate eligibility | |
| Listed for battery storage on Synergy's list | Yes |
| Installation requirements | |
| Top clearance | 300 mm |
| Side clearance | 300 mm |
| AC breaker | 50 A |
| Cable gauge | 10 mm² |
| Earthing method | TN-S |
| DNSP pre-approval | Yes |
| Estimated install time | 8 hrs |
Parsed from the manufacturer datasheet, install manual, and warranty document. Confirm against the linked PDFs before relying on a value for a quote or installation.
How it compares
The Neovolt BW-INV-SPH5K against the closest-power inverters from other brands.
| Specification | Neovolt BW-INV-SPH5KNeovolt | Energizer FORCE 5.0HSEnergizer | Energizer Force 5.0HT+Energizer |
|---|---|---|---|
| Rated power? | 5 kW | 5 kW | 5 kW |
| Max efficiency? | 97.0% | Not on file | Not on file |
| MPPT trackers? | Not on file | Not on file | Not on file |
| Phases | Single-phase | Single-phase | Three-phase |
| Type | Hybrid | Hybrid | Hybrid |
| Battery ready | Yes | Yes | Yes |
| Warranty | 10 years | Not on file | Not on file |
Specs from the CEC register and datasheet enrichment. Indicative: confirm exact figures with your installer.
10-year inverter warranty
Neovolt BW-INV-SPH5KThis warranty covers inverter performance for 10 years. Capacity retention must be above 80%, and claims can be made by contacting support.
AI-summarised from the manufacturer warranty document. Always confirm against the linked PDF before relying on it for a claim.
- Coverage shape
- Full-replacement coverage
- If you sell the home
- Transfers to the next homeowner
- What voids it
- Non-accredited installation, modification, or tampering.
- Environment limits
- Operating Temperature Range: -20~60°C, voids if exceeded.
Fault & error codes — Neovolt BW-INV-SPH5K
From the install manual
Showing 45 of 45. The official install manual is the authoritative source — always confirm before acting.
- Manual (PDF)
100005criticalCall your installerBus over voltage protection
- Likely cause
- Check whether the input voltage of PV1 and PV2 exceeds 580V. Restart the inverter to see if the fault persists, if not call the service center.
- What to do
- Inspect PV input voltage and restart the inverter.
- Manual (PDF)
100007criticalCall your installerInsulation fault
- Likely cause
- Check whether the PV cable connection is reliable. Check whether the PV cable is damaged.
- What to do
- Inspect the integrity of the PV cables.
- Manual (PDF)
100011criticalCall your installerOver temperature
- Likely cause
- Check the environment around the inverter for poor heat dissipation.
- What to do
- Ensure proper ventilation around the inverter.
- Manual (PDF)
100017criticalCall your installerMPPT1 over voltage protection
- Likely cause
- Check the PV1 voltage, if it exceeds 585V reduce the number of PV panels.
- What to do
- Inspect and adjust PV setup.
- Manual (PDF)
100018criticalCall your installerMPPT1 switch over current protection
- Likely cause
- Try to reduce the PV power. Restart the inverter to check if the fault persists.
- What to do
- Lower the PV power and restart the inverter.
- Manual (PDF)
100019criticalCall your installerMPPT1 hardware over current protection
- Likely cause
- Try to reduce the PV power. Restart the inverter to check if the fault persists.
- What to do
- Lower the PV power and restart the inverter.
- Manual (PDF)
100020criticalCall your installerMPPT1 over temperature protection
- Likely cause
- Try to lower the ambient temperature around the inverter.
- What to do
- Ensure the inverter is properly ventilated and cool.
- Manual (PDF)
100021criticalCall your installerMPPT2 over voltage protection
- Likely cause
- Check the PV2 voltage. If it exceeds 585V reduce the number of PV modules.
- What to do
- Inspect and adjust PV setup.
- Manual (PDF)
100022criticalCall your installerMPPT2 switch over current protection
- Likely cause
- Try to reduce the PV power. Restart the inverter to check if the fault persists.
- What to do
- Lower the PV power and restart the inverter.
- Manual (PDF)
100023criticalCall your installerMPPT2 hardware over current protection
- Likely cause
- Try to reduce the PV power. Restart the inverter to check if the fault persists.
- What to do
- Lower the PV power and restart the inverter.
- Manual (PDF)
100024criticalCall your installerMPPT2 over temperature protection
- Likely cause
- Try to lower the ambient temperature around the inverter.
- What to do
- Ensure the inverter is properly ventilated and cool.
- Manual (PDF)
100025criticalCall your installerBattery over voltage protection
- Likely cause
- Check if the battery voltage exceeds the charging cut-off by more than 20V.
- What to do
- Inspect battery voltage settings and connections.
- Manual (PDF)
100026criticalCall your installerBattery under voltage protection
- Likely cause
- Check if the battery voltage is lower than the discharge cut-off.
- What to do
- Inspect battery voltage settings and connections.
- Manual (PDF)
100027criticalCall your installerBattery loss
- Likely cause
- Confirm that wiring is normal and check if battery voltage sampling is less than 75V.
- What to do
- Inspect battery connections and voltage.
- Manual (PDF)
100028criticalCall your installerBattery over temperature protection
- Likely cause
- Try to lower the ambient temperature around the inverter.
- What to do
- Ensure the inverter is properly ventilated and cool.
- Manual (PDF)
100029criticalCall your installerBattery 1 charge over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100030criticalCall your installerBattery 1 discharge over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100031criticalCall your installerBattery 2 charge over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100032criticalCall your installerBattery 2 discharge over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100033criticalCall your installerBattery 1 hardware over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100034criticalCall your installerBattery 2 hardware over current protection
- Likely cause
- Try to reduce battery power in use.
- What to do
- Lower battery usage power and restart the inverter.
- Manual (PDF)
100035criticalCall your installerInverter over temperature protection
- Likely cause
- Try to lower the ambient temperature around the inverter.
- What to do
- Ensure proper ventilation and cooling for inverter.
- Manual (PDF)
100036criticalCall your installerGrid max voltage protection
- Likely cause
- Check grid voltage and connections. Might indicate a grid issue.
- What to do
- Consult with utility service provider regarding grid conditions.
- Manual (PDF)
100037criticalCall your installerInverter under voltage protection
- Likely cause
- Check for short circuits or impact load on off-grid terminals.
- What to do
- Inspect connections and loads on the inverter.
- Manual (PDF)
100038criticalCall your installerOutput DC over current protection
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Inspect output connections and load.
- Manual (PDF)
100039criticalCall your installerInverter over current protection
- Likely cause
- Check for overloads or short circuits on inverter terminals.
- What to do
- Inspect load and connections, then restart.
- Manual (PDF)
100040criticalCall your installerInverter hardware over current protection
- Likely cause
- Check for overloads or short circuits on inverter terminals.
- What to do
- Inspect load and connections, then restart.
- Manual (PDF)
100041criticalCall your installerOutput DC over voltage protection
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Inspect configurations and connections for voltage spikes.
- Manual (PDF)
100042criticalCall your installerOutput short circuit
- Likely cause
- Check load connections; possibly a wiring issue.
- What to do
- Inspect connections and rectify faults.
- Manual (PDF)
100043criticalCall your installerOutput overload
- Likely cause
- Check if load exceeds the rated power of the inverter.
- What to do
- Reduce load and ensure proper settings on the inverter.
- Manual (PDF)
100000warningGrid over voltage protection
- Likely cause
- Check whether the grid is abnormal. Confirm whether the grid cable connection is normal. Restart the inverter and check if the fault persists.
- What to do
- Check grid status and cable connections, then restart the inverter.
- Manual (PDF)
100001warningGrid under voltage protection
- Likely cause
- Check whether the grid is abnormal. Confirm whether the grid cable connection is normal. Restart the inverter and check if the fault persists.
- What to do
- Check grid status and cable connections, then restart the inverter.
- Manual (PDF)
100002warningGrid over frequency protection
- Likely cause
- Check whether the grid is abnormal. Confirm whether the grid cable connection is normal. Restart the inverter and check if the fault persists.
- What to do
- Check grid status and cable connections, then restart the inverter.
- Manual (PDF)
100003warningGrid under frequency protection
- Likely cause
- Check whether the grid is abnormal. Confirm whether the grid cable connection is normal. Restart the inverter and check if the fault persists.
- What to do
- Check grid status and cable connections, then restart the inverter.
- Manual (PDF)
100008warningGFCI fault
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Restart the inverter.
- Manual (PDF)
100009warningLeakage current test failure
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Restart the inverter.
- Manual (PDF)
100010warningGrid relay fault
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Restart the inverter.
- Manual (PDF)
100014warningCommunication fault
- Likely cause
- Restart the inverter and check if the fault persists.
- What to do
- Restart the inverter.
- Manual (PDF)
110000warningBattery over voltage alarm
- Likely cause
- Check battery voltage against the cut-off point.
- What to do
- Inspect battery settings and voltage levels.
- Manual (PDF)
110001warningBattery under voltage alarm
- Likely cause
- Check battery voltage against the cut-off point.
- What to do
- Inspect battery settings and voltage levels.
- Manual (PDF)
110002warningOutput overload alarm
- Likely cause
- Evaluate load against inverter capacity.
- What to do
- Reduce load on inverter and monitor.
- Manual (PDF)
110003warningAbnormal temperature sensor alarm
- Likely cause
- Inspect temperature sensor connections and integrity.
- What to do
- Check sensor functionality.
- Manual (PDF)
110004warningDC power alarm
- Likely cause
- Total power of battery and PV is less than load power.
- What to do
- Evaluate generated vs consumption power.
- Manual (PDF)
110005warningBattery stops running alarm
- Likely cause
- Check battery connections and voltage.
- What to do
- Ensure battery is connected and functional.
- Manual (PDF)
110006warningOver temperature alarm
- Likely cause
- Check ambient temperature around inverter.
- What to do
- Ensure voltage and thermal management on inverter is effective.
More Neovolt inverters
BW-INV-SPB5K (AS4777-2 2020)
5 kW · 1φ
BW-INV-SPB5K (AS4777-2 2020)
5 kW · 1φ
BW-INV-SPH5K (AS4777-2 2020)
5 kW · 1φ
BW-INV-SPH6K (AS4777-2 2020)
6 kW · 1φ
BW-INV-SPH6K1 (AS4777-2 2020)
6 kW · 1φ
BW-INV-SPH3.6K (AS4777-2 2020)
3.68 kW · 1φ
More from Neovolt
Other CEC-approved products from Neovolt available in Australia.
Want to take the next step?
Get a quote from a member installer who covers your area. You choose whether to act on it. No obligation.
About this data
All inverter specifications are sourced from the CEC Approved Products Register. Specifications are provided as published by the CEC and may differ from manufacturer datasheets. Verify current specifications with the manufacturer or your installer before purchasing. Not all listed models may be currently available in Western Australia.