Skip to main content
Solar Battery PerthSolar Battery Perth
  • Library
  • Compare
  • Calculate savings
  • Quote
  • Tools
Battery matcher
Battery matcher

Rebate and policy updates by email

What's changing with WA rebates and battery rules, for Perth homeowners.

Solar Battery Perth

WA-specific solar and battery tools with transparent installer matching for Synergy and Western Power customers.

  • 08 9429 8803
  • info@solarbatteryperth.com.au
Explore your optionsCompare products

Tools

  • Solar system quiz
  • Side-by-side comparison
  • Savings calculator
  • Tariff comparison
  • VPP earnings
  • Quote evaluator
  • Warranty comparison
  • Library
  • Product search
  • All tools

Information

  • How it works
  • Resources
  • WA rebates & incentives
  • Battery price index
  • Synergy tariffs
  • Financing
  • Getting started
  • Buyer's guide
  • Solar and battery integration
  • Battery scenarios

Get started

  • Find installers
  • Perth suburbs
  • Brands
  • Contact us
  • Common questions
Privacy policyTerms of useDisclaimerReview policyAffiliate disclosureAccessibility

© 2026 Solar Battery Perth, operated by WattMate Pty Ltd. Independent solar and battery resource for WA homeowners.

Installers pay us a flat $30 including GST per accepted lead, the same for every installer and every system. How it works

45 Ventnor Avenue, West Perth WA 6005

  • Home
  • Library
  • Compare
  • Savings
  • Quote
  1. Home
  2. Inverters
  3. Yinergy Digital Power Technology
  4. HI-1P5K-L-Y1

Hybrid inverter · Yinergy Digital Power Technology · CEC approved June 2026

Yinergy Digital Power Technology HI-1P5K-L-Y1

CEC listing: HI-1P5K-L-Y1 (AS4777-2 2020)

A 5 kW single-phase hybrid inverter that is battery-ready.

Rated power
5kWHow much solar it can run at once
Battery-ready
YesHybrid: a battery plugs straight in, no second box
Datasheet (PDF)

Get this inverter quoted in Perth

Enter your postcode and get a free, no-obligation quote from a member installer who covers your area.

HI-1P5K-L-Y1: the short answer

Feed-in credits (DEBS)DEBS pays for exports only when the inverter is 5 kW or less
YesDEBS pays for exports only when the inverter is 5 kW or less

What we can tell you

Read from the figures on this page. No review written yet.

  • It is a hybrid inverter: solar and a battery run from the one unit, so adding a battery later doesn't need a second box.
  • It runs on a standard single-phase supply.
  • It is CEC-approved, which a new install needs to qualify for STCs.

Key specs, in plain terms

The numbers that matter for a home. The full datasheet is below.

Rated power
5kW
How much solar it can turn into usable power at once
Max efficiency
Not on file: we don't have this figure from the manufacturer's documents yet
How much of the solar you make reaches the house
Phases
Single
Runs on a standard single-phase supply
Type
Hybrid
Runs solar and a battery from one unit
Warranty
10yr
How long Yinergy Digital Power Technology Co Ltd stands behind it

Not on file: we don’t have this figure from the manufacturer’s documents yet, so we leave it blank rather than print a typical value. Ask your installer to confirm it on the quote. Seen it in a document? Tell us

Full datasheet

Every figure on file for the Yinergy Digital Power Technology HI-1P5K-L-Y1, by section.

Full datasheet, by section
SpecificationValue
Physical
IP ratingIP66
Installation requirements
Top clearance300 mm
Side clearance300 mm
AC breaker25 A
Cable gauge4 mm²
Earthing methodClass I
DNSP pre-approvalYes
Estimated install time8 hrs

Parsed from the manufacturer datasheet, install manual, and warranty document. Confirm against the linked PDFs before relying on a value for a quote or installation.

Features and CEC approval

Battery compatible
Yes
Backup capable
Yes
CEC approved
5 June 2026
Approval expiry
5 June 2029
Status
Active
Listed for STCs
Yes

About Yinergy Digital Power Technology

Australian office
Not verified
Category
Unknown
CEC-approved inverters
6
View full profile →
Explore your options

Get a quote from an installer sourced from the WA (Synergy/Plenti) approved list

  • Compare with other inverters→
  • Already have a quote? Check it→
  • Browse CEC-approved panels→

WA compliance

ESM compliant
Check

Western Power approval is required for every grid-connected install. Under Emergency Solar Management, a new system must be remotely manageable, or take an export limit instead. Ask your installer to confirm this inverter’s ESM status.

Perth performance

Estimate for a full-size array on this inverter

Daily yield
21.3 kWh
Annual yield
7,756 kWh

At 5 peak sun hours a day (BOM) with a 15% system derate.

0 years on the CEC list

How it compares

The Yinergy Digital Power Technology HI-1P5K-L-Y1 against the closest-power inverters from other brands.

Specification
Yinergy Digital Power Technology HI-1P5K-L-Y1Yinergy Digital Power Technology
Energizer FORCE 5.0HSEnergizer
Energizer Force 5.0HT+Energizer
Rated power?5 kW5 kW5 kW
Max efficiency?Not on fileNot on fileNot on file
MPPT trackers?Not on fileNot on fileNot on file
PhasesSingle-phaseSingle-phaseThree-phase
TypeHybridHybridHybrid
Battery readyYesYesYes
Warranty10 yearsNot on fileNot on file

Specs from the CEC register and datasheet enrichment. Indicative: confirm exact figures with your installer.

Documents

  • DatasheetPDF, opens in a new tab
  • Warranty termsPDF, opens in a new tab
  • Installation guidePDF, opens in a new tab
  • User manualPDF, opens in a new tab
  • Compliance certificatePDF, opens in a new tab

10-year inverter warranty

Yinergy Digital Power Technology HI-1P5K-L-Y1

This warranty covers defects in materials and workmanship for ten years. Not covered: installations not per local codes. Claims can be made via an authorized dealer.

AI-summarised from the manufacturer warranty document. Always confirm against the linked PDF before relying on it for a claim.

Coverage shape
Full-replacement coverage
If you sell the home
Transfers to the next homeowner
What voids it
Non-accredited installations, improper maintenance, misuse, unauthorized alterations, incorrect servicing, operation outside owner's manual instructions.
Environment limits
Corrosive environments, except for coastal rated units in coastal environments.
Read the official warranty document (PDF)

Fault & error codes — Yinergy Digital Power Technology HI-1P5K-L-Y1

From the install manual

70 documented

Showing 70 of 70. The official install manual is the authoritative source — always confirm before acting.

  • ARM EEPROM FaultcriticalCall your installer
    Manual (PDF)

    The manager eeprom is fault.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Bat Boost FaultcriticalCall your installer
    Manual (PDF)

    The battery boost circuit mosfet is fail.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Bat Buck FaultcriticalCall your installer
    Manual (PDF)

    The battery buck circuit mosfet is fail.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Bms ChgCur HighcriticalCall your installer
    Manual (PDF)

    Battery charge over current.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms ChgReq NoAckcriticalCall your installer
    Manual (PDF)

    No action for charging request.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms DchgCur HighcriticalCall your installer
    Manual (PDF)

    Battery discharge over current.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms HW ProtectcriticalCall your installer
    Manual (PDF)

    Battery hardware under protection.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Insul FaultcriticalCall your installer
    Manual (PDF)

    Battery insulation fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms M&S UnmatchcriticalCall your installer
    Manual (PDF)

    The software between Master and Slave are not match.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Mfg UnmatchcriticalCall your installer
    Manual (PDF)

    The cell manufacture is different.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Relay FaultcriticalCall your installer
    Manual (PDF)

    Battery relay fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms SwHw UnmatchcriticalCall your installer
    Manual (PDF)

    The slave software and hardware are not match.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Temp HighcriticalCall your installer
    Manual (PDF)

    Battery over temperature.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Temp LowcriticalCall your installer
    Manual (PDF)

    Battery under temperature.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Type UnmatchcriticalCall your installer
    Manual (PDF)

    The capacity of battery packs is different.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Ver UnmatchcriticalCall your installer
    Manual (PDF)

    The software between slaves are different.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Volt HighcriticalCall your installer
    Manual (PDF)

    Battery over voltage.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Bms Volt LowcriticalCall your installer
    Manual (PDF)

    Battery under voltage.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • BmsCellImbalancecriticalCall your installer
    Manual (PDF)

    The capacities of cells are different.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • BmsCircuit FaultcriticalCall your installer
    Manual (PDF)

    Bms hardware circuit fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • BmsCurSen FaultcriticalCall your installer
    Manual (PDF)

    Battery current sensor fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • BmsTempSen FaultcriticalCall your installer
    Manual (PDF)

    Battery temperature sensor fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • BmsVoltsSen FaultcriticalCall your installer
    Manual (PDF)

    Battery voltage sensor fault.

    Likely cause
    Please contact battery supplier.
    What to do
    Seek help from support.
  • Dci Cons FaultcriticalCall your installer
    Manual (PDF)

    The dci sample value between master and slave is not consistent.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Eps Over LoadcriticalCall your installer
    Manual (PDF)

    Over load in off grid mode.

    Likely cause
    Please check if the eps load power exceeds the limit.
    What to do
    Seek help from support.
  • Eps Relay FaultcriticalCall your installer
    Manual (PDF)

    The eps relay is failed.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • GridF Cons FaultcriticalCall your installer
    Manual (PDF)

    The grid frequency sample value between master and slave is not consistent.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • GridV Cons FaultcriticalCall your installer
    Manual (PDF)

    The grid voltage sample value between master and slave is not consistent.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Ground FaultcriticalCall your installer
    Manual (PDF)

    The ground connection is failed.

    Likely cause
    Check the voltage of neutral and PE.
    What to do
    Disconnect PV, grid and battery, then reconnect. Or seek help from support.
  • Inv EEPROM FaultcriticalCall your installer
    Manual (PDF)

    The inverter eeprom is fault.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Iso FaultcriticalCall your installer
    Manual (PDF)

    The isolation is failed.

    Likely cause
    Please check if the insulation of electric wires is damaged.
    What to do
    Wait for a while to check if back to normal. Or seek help from support.
  • MDSP Smpl FaultcriticalCall your installer
    Manual (PDF)

    The master sample detection circuit is failed.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • MDSP SPI FaultcriticalCall your installer
    Manual (PDF)

    The communication between master and slave is fail.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Over Load FaultcriticalCall your installer
    Manual (PDF)

    Over load in on grid mode.

    Likely cause
    Please check if the load power exceeds the limit.
    What to do
    Seek help from support.
  • Rc Cons FaultcriticalCall your installer
    Manual (PDF)

    The residual current sample value between master and slave is not consistent.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • RDSP Smpl FaultcriticalCall your installer
    Manual (PDF)

    The slave sample detection circuit is failed.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • RDSP SPI FaultcriticalCall your installer
    Manual (PDF)

    The communication between master and slave is fail.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Res Cur FaultcriticalCall your installer
    Manual (PDF)

    The residual current is high.

    Likely cause
    Please check if the insulation of electric wires is damaged.
    What to do
    Wait for a while to check if back to normal. Or seek help from support.
  • Res Cur HW FaultcriticalCall your installer
    Manual (PDF)

    Residual current detection device is failed.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • SCI FaultcriticalCall your installer
    Manual (PDF)

    The communication between master and manager is fail.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • 10min Volt Faultwarning
    Manual (PDF)

    The grid voltage is out of range for the last 10 Minutes.

    Likely cause
    System will reconnect if the utility is back to normal.
    What to do
    Seek help from support if it does not return to normal.
  • Bat Power Lowwarning
    Manual (PDF)

    The battery power is low.

    Likely cause
    Battery needs recharge.
    What to do
    Wait for the battery to be recharged. Or seek help from support.
  • Bat Relay OpenwarningCall your installer
    Manual (PDF)

    The battery relay keeps open.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Bat Relay Short CircuitwarningCall your installer
    Manual (PDF)

    The battery relay keeps close.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Bat Volt FaultwarningCall your installer
    Manual (PDF)

    Battery voltage fault.

    Likely cause
    Check if the battery input voltage is within the normal range.
    What to do
    Seek help from support.
  • BatCon Dir FaultwarningCall your installer
    Manual (PDF)

    The battery connection is reversed.

    Likely cause
    Check if the positive pole and negative pole of battery are correctly connected.
    What to do
    Seek help from support.
  • Bms Ext FaultwarningCall your installer
    Manual (PDF)

    The communication between BMS and Inverter is interrupted.

    Likely cause
    Check if the communication cable between BMS and Inverter is correctly and well connected.
    What to do
    Seek help from support.
  • Bms Int FaultwarningCall your installer
    Manual (PDF)

    DIP switch at the wrong position; The communication between battery packs is interrupted.

    Likely cause
    Move the DIP switch to the correct position; Check if the communication cable between battery packs is correctly and well connected.
    What to do
    Seek help from support.
  • BMS LostwarningCall your installer
    Manual (PDF)

    The communication between BMS and Inverter is interrupted.

    Likely cause
    Check if the communication cable between BMS and Inverter is correctly and well connected.
    What to do
    Seek help from support.
  • DCI FaultwarningCall your installer
    Manual (PDF)

    DC component is out of limit in output current.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Grid Freq Faultwarning
    Manual (PDF)

    Grid frequency out of range.

    Likely cause
    System will reconnect if the utility is back to normal.
    What to do
    Seek help from support if it does not return to normal.
  • Grid Lost Faultwarning
    Manual (PDF)

    Grid is lost.

    Likely cause
    System will reconnect if the utility is back to normal.
    What to do
    Seek help from support if it does not return to normal.
  • Grid Volt Faultwarning
    Manual (PDF)

    Grid voltage out of range.

    Likely cause
    System will reconnect if the utility is back to normal.
    What to do
    Seek help from support if it does not return to normal.
  • HW Bat Cur FaultwarningCall your installer
    Manual (PDF)

    Battery current high detected by hardware.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • HW Bus Vol FaultwarningCall your installer
    Manual (PDF)

    Bus voltage out of range detected by hardware.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • HW Inv Cur FaultwarningCall your installer
    Manual (PDF)

    Output current high detected by hardware.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • HW Pv Cur FaultwarningCall your installer
    Manual (PDF)

    PV input current high detected by hardware.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • M1 Close FaultwarningCall your installer
    Manual (PDF)

    The grid relay M1 keep close.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • M2 Close FaultwarningCall your installer
    Manual (PDF)

    The grid relay M2 keep close.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Main Relay OpenwarningCall your installer
    Manual (PDF)

    The grid relay keeps open.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Meter Lost FaultwarningCall your installer
    Manual (PDF)

    The communication between meter and Inverter is interrupted.

    Likely cause
    Check if the communication cable between meter and Inverter is correctly and well connected.
    What to do
    Seek help from support.
  • Pv Volt FaultwarningCall your installer
    Manual (PDF)

    PV voltage out of range.

    Likely cause
    Please check the output voltage of PV panels.
    What to do
    Seek help from support.
  • PvCon Dir FaultwarningCall your installer
    Manual (PDF)

    The PV connection is reversed.

    Likely cause
    Check if the positive pole and negative pole of PV are correctly connected.
    What to do
    Seek help from support.
  • S1 Close FaultwarningCall your installer
    Manual (PDF)

    The grid relay S1 keep close.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • S2 Close FaultwarningCall your installer
    Manual (PDF)

    The grid relay S2 keep close.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • SW Bat Cur FaultwarningCall your installer
    Manual (PDF)

    Battery current high detected by software.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • SW Bus Vol FaultwarningCall your installer
    Manual (PDF)

    Bus voltage out of range detected by software.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • SW Inv Cur FaultwarningCall your installer
    Manual (PDF)

    Output current high detected by software.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • SW Pv Cur FaultwarningCall your installer
    Manual (PDF)

    PV input current high detected by software.

    Likely cause
    Disconnect PV, grid and battery, then reconnect.
    What to do
    Seek help from support if it does not return to normal.
  • Temp Faultwarning
    Manual (PDF)

    The inverter temperature is high.

    Likely cause
    Please check if the environment temperature is appropriate.
    What to do
    Wait for a while to check if back to normal. Or seek help from support.

More Yinergy Digital Power Technology Co Ltd inverters

HI-1P4.6K-L-Y1 (AS4777-2 2020)

4.6 kW · 1φ

HI-1P4K-L-Y1 (AS4777-2 2020)

4 kW · 1φ

HI-1P6K-L-Y1 (AS4777-2 2020)

6 kW · 1φ

HI-1P3.68K-L-Y1 (AS4777-2 2020)

3.68 kW · 1φ

HI-1P3K-L-Y1 (AS4777-2 2020)

3 kW · 1φ

View all Yinergy Digital Power Technology Co Ltd inverters

Want to take the next step?

Get a quote from a member installer who covers your area. You choose whether to act on it. No obligation.

We collect these details to prepare your quote match and to share with the installer(s) we match you with. Not providing them means we can't match you. Full collection notice.

Or explore your battery options first →

By requesting quotes you agree to be contacted by installers in our network about your enquiry. Part of WattMate Pty Ltd. No spam, opt out any time.

About this data

All inverter specifications are sourced from the CEC Approved Products Register. Specifications are provided as published by the CEC and may differ from manufacturer datasheets. Verify current specifications with the manufacturer or your installer before purchasing. Not all listed models may be currently available in Western Australia.

Explore your optionsCompare inverters
Spotted something outdated?