Skip to main content
Solar Battery PerthSolar Battery Perth
  • Library
  • Compare
  • Calculate savings
  • Quote
  • Tools
Battery matcher
Battery matcher

Rebate and policy updates by email

What's changing with WA rebates and battery rules, for Perth homeowners.

Solar Battery Perth

WA-specific solar and battery tools with transparent installer matching for Synergy and Western Power customers.

  • 08 9429 8803
  • info@solarbatteryperth.com.au
Explore your optionsCompare products

Tools

  • Solar system quiz
  • Side-by-side comparison
  • Savings calculator
  • Tariff comparison
  • VPP earnings
  • Quote evaluator
  • Warranty comparison
  • Library
  • Product search
  • All tools

Information

  • How it works
  • Resources
  • WA rebates & incentives
  • Battery price index
  • Synergy tariffs
  • Financing
  • Getting started
  • Buyer's guide
  • Solar and battery integration
  • Battery scenarios

Get started

  • Find installers
  • Perth suburbs
  • Brands
  • Contact us
  • Common questions
Privacy policyTerms of useDisclaimerReview policyAffiliate disclosureAccessibility

© 2026 Solar Battery Perth, operated by WattMate Pty Ltd. Independent solar and battery resource for WA homeowners.

Installers pay us a flat $30 including GST per accepted lead, the same for every installer and every system. How it works

45 Ventnor Avenue, West Perth WA 6005

  • Home
  • Library
  • Compare
  • Savings
  • Quote
  1. Home
  2. Inverters
  3. GoodWe
  4. GW3600-SBP-20

Battery inverter · GoodWe · CEC approved March 2026

GoodWe GW3600-SBP-20

CEC listing: GW3600-SBP-20 (AS4777-2 2020)

A 3.7 kW single-phase battery inverter that is listed for battery storage on Synergy's list.

Listed for battery storage on Synergy's list
YesSynergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.
Rated power
3.7kWHow much solar it can run at once
Battery-ready
YesBattery inverter: it runs the battery, alongside your solar inverter
Datasheet (PDF)

Get this inverter quoted in Perth

Enter your postcode and get a free, no-obligation quote from a member installer who covers your area.

GW3600-SBP-20: the short answer

Listed for battery storage on Synergy's listMatched to this exact model. Other scheme conditions apply
YesMatched to this exact model. Other scheme conditions apply

What we can tell you

Read from the figures on this page. No review written yet.

  • It is a battery inverter: it runs a battery, and pairs with a separate solar inverter.
  • It runs on a standard single-phase supply.
  • Listed for battery storage on Synergy's list. Synergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.
  • It is CEC-approved, which a new install needs to qualify for STCs.

Key specs, in plain terms

The numbers that matter for a home. The full datasheet is below.

Rated power
3.7kW
How much solar it can turn into usable power at once
Max efficiency
Not on file: we don't have this figure from the manufacturer's documents yet
How much of the solar you make reaches the house
Phases
Single
Runs on a standard single-phase supply
Type
Battery
Runs a battery; pairs with a separate solar inverter
Warranty
5yr
How long GoodWe Technologies Co Ltd stands behind it

Not on file: we don’t have this figure from the manufacturer’s documents yet, so we leave it blank rather than print a typical value. Ask your installer to confirm it on the quote. Seen it in a document? Tell us

Full datasheet

Every figure on file for the GoodWe GW3600-SBP-20, by section.

Full datasheet, by section
SpecificationValue
Physical
IP ratingIP65
Rebate eligibility
Listed for battery storage on Synergy's listYes
Installation requirements
Top clearance300 mm
Side clearance200 mm
AC breaker40 A
Cable gauge6 mm²
Earthing methodTN-S
DNSP pre-approvalYes
Estimated install time6 hrs

Parsed from the manufacturer datasheet, install manual, and warranty document. Confirm against the linked PDFs before relying on a value for a quote or installation.

Features and CEC approval

Battery compatible
Yes
Backup capable
Yes
CEC approved
27 Mar 2026
Approval expiry
19 Aug 2027
Status
Active
Listed for STCs
Yes

About GoodWe

Years on the CEC list
12 years
Australian office
Yes
Category
Mid-Tier
CEC-approved inverters
229
CEC-approved batteries
30
CEC-approved panels
168
View full profile →
Explore your options

Get a quote from an installer sourced from the WA (Synergy/Plenti) approved list

  • Compare with other inverters→
  • Already have a quote? Check it→
  • GoodWe Technologies Co Ltd batteries and panels→

WA compliance

Listed for battery storage on Synergy's list
Yes
ESM compliant
Check

Listed for battery storage on Synergy's list. Synergy's Supported Solutions List covers inverters approved for control. A battery system needs an inverter with a battery-storage (DER-Storage) listing on this list to be eligible for the WA Battery Scheme. A listing for generation only doesn't count. Other scheme conditions apply.Western Power approval is required for every grid-connected install. Under Emergency Solar Management, a new system must be remotely manageable, or take an export limit instead. Ask your installer to confirm this inverter’s ESM status.

Perth performance

Estimate for a full-size array on this inverter

Daily yield
15.6 kWh
Annual yield
5,709 kWh

At 5 peak sun hours a day (BOM) with a 15% system derate.

Australian office

Has local presence

Website

www.goodwe.com.au
12 years on the CEC list

How it compares

The GoodWe GW3600-SBP-20 against the closest-power inverters from other brands.

Specification
GoodWe GW3600-SBP-20GoodWe
Energizer FORCE 3.7HSEnergizer
Solplanet ASW3680-SSolplanet
Rated power?3.68 kW3.68 kW3.68 kW
Max efficiency?Not on fileNot on fileNot on file
MPPT trackers?Not on fileNot on fileNot on file
PhasesSingle-phaseSingle-phaseSingle-phase
TypeBatteryHybridSolar
Battery readyYesYesNo
Warranty5 yearsNot on fileNot on file

Specs from the CEC register and datasheet enrichment. Indicative: confirm exact figures with your installer.

Documents

  • DatasheetPDF, opens in a new tab
  • Warranty termsPDF, opens in a new tab
  • Installation guidePDF, opens in a new tab
  • User manual and compliance certificatePDF, opens in a new tab

5-year inverter warranty

GoodWe GW3600-SBP-20

GoodWe provides a 5-year warranty for inverters against manufacturing defects. Major exclusions include improper installation and environmental damage. Claims can be made through the local distributor or installer.

AI-summarised from the manufacturer warranty document. Always confirm against the linked PDF before relying on it for a claim.

Coverage shape
Full-replacement coverage
If you sell the home
Transfers to the next homeowner
What voids it
Non-accredited installation, modifications, tampering, improper handling, or operation against instructions.
Environment limits
Rust from harsh environmental conditions, defects from exposure to saltwater without prior approval.
Read the official warranty document (PDF)

Fault & error codes — GoodWe GW3600-SBP-20

From the install manual

34 documented

Showing 34 of 34. The official install manual is the authoritative source — always confirm before acting.

  • 10criticalCall your installer
    Manual (PDF)

    LVRT Undervoltage

    Likely cause
    Utility grid exception. The duration of the utility grid exception exceeds the set time of LVRT.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. If the problem occurs frequently, check whether the grid frequency is within the permissible range or contact the local power company.
  • 11criticalCall your installer
    Manual (PDF)

    HVRT Overvoltage

    Likely cause
    Utility grid exception. The duration of utility grid exception exceeds the set time of HVRT.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. If the problem persists, check whether the grid frequency is within the permissible range or contact the dealer or after-sales service.
  • 16criticalCall your installer
    Manual (PDF)

    Large DC of AC current L1

    Likely cause
    The DC component of the output current exceeds the safety range or default range.
    What to do
    If the problem occurs frequently and the PV station cannot work properly, contact the dealer or after-sales service.
  • 17criticalCall your installer
    Manual (PDF)

    Large DC of AC current L2

    Likely cause
    The DC component of the output current exceeds the safety range or default range.
    What to do
    If the problem occurs frequently and the PV station cannot work properly, contact the dealer or after-sales service.
  • 2criticalCall your installer
    Manual (PDF)

    Grid Overvoltage

    Likely cause
    The grid voltage exceeds the permissible range, or the duration of high voltage exceeds the requirement of HVRT.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Check whether the grid voltage is within the permissible range. Contact the local power company if the grid voltage exceeds the permissible range.
  • 24criticalCall your installer
    Manual (PDF)

    Relay Check abnormal

    Likely cause
    The relay is abnormal or short-circuited.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 26criticalCall your installer
    Manual (PDF)

    Flash Fault

    Likely cause
    The internal Flash storage is abnormal.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 29criticalCall your installer
    Manual (PDF)

    Cavity Overtemperature

    Likely cause
    The inverter is installed in a place with poor ventilation.
    What to do
    Check the ventilation and the ambient temperature at the installation point. Contact the dealer or after-sales service if both ventilation and temperature are normal.
  • 3criticalCall your installer
    Manual (PDF)

    Grid Rapid Overvoltage

    Likely cause
    The grid voltage is abnormal or ultra-high.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. If the problem occurs frequently, check whether the grid voltage is within the permissible range. Contact the local power company if necessary.
  • 30criticalCall your installer
    Manual (PDF)

    BUS Overvoltage

    Likely cause
    The PV voltage is too high.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 31criticalCall your installer
    Manual (PDF)

    PV Input Overvoltage

    Likely cause
    The PV array configuration is not correct, too many PV panels are connected in series in the PV string.
    What to do
    Check the serial connection of the PV array. Make sure that the open circuit voltage of the PV string is not higher than the maximum operating voltage of the inverter.
  • 32criticalCall your installer
    Manual (PDF)

    PV Continuous Hardware Overcurrent

    Likely cause
    The PV configuration or hardware is damaged.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact dealer or after-sales service if problems persist.
  • 33criticalCall your installer
    Manual (PDF)

    PV Continuous Software Overcurrent

    Likely cause
    The PV configuration or hardware is damaged.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact dealer or after-sales service if problems persist.
  • 4criticalCall your installer
    Manual (PDF)

    Grid Undervoltage

    Likely cause
    The grid voltage is lower than the permissible range, or the duration of low voltage exceeds the requirement of LVRT.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Check whether the grid voltage is within the permissible range and contact the local power company if necessary.
  • 5criticalCall your installer
    Manual (PDF)

    Grid 10min Overvoltage

    Likely cause
    The moving average of grid voltage in 10min exceeds the range of safety requirements.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Contact the local power company if necessary.
  • 6criticalCall your installer
    Manual (PDF)

    Grid Overfrequency

    Likely cause
    Utility grid exception. The actual grid frequency exceeds the requirement of the local grid standard.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Check whether the grid frequency is within the permissible range and contact the power company if necessary.
  • 7criticalCall your installer
    Manual (PDF)

    Grid Underfrequency

    Likely cause
    Utility grid exception. The actual grid frequency is lower than the requirement of the local grid standard.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Contact the local power company regarding the grid frequency if necessary.
  • 8criticalCall your installer
    Manual (PDF)

    Grid Frequency Instability

    Likely cause
    Utility grid exception. The actual grid frequency change rate does not meet the requirement of the local grid standard.
    What to do
    If the problem occurs occasionally, the inverter will recover automatically after detecting that the utility grid is normal. Contact the dealer or after-sales service if the problem persists.
  • 1warning
    Manual (PDF)

    Utility Loss

    Likely cause
    Utility grid power fails. The AC cable is disconnected, or the AC breaker is off.
    What to do
    The alarm is automatically cleared after the grid power supply is restored. Check whether the AC cable is connected and the AC breaker is on.
  • 12warning
    Manual (PDF)

    Abnormal GFCI 30mA

    Likely cause
    The input insulation impedance to the ground decreases while the inverter is working.
    What to do
    If the problem persists, check whether the impedance between the PV string and PE is too low.
  • 13warning
    Manual (PDF)

    Abnormal GFCI 60mA

    Likely cause
    The input insulation impedance to the ground decreases while the inverter is working.
    What to do
    If the problem persists, check whether the impedance between the PV string and PE is too low.
  • 14warning
    Manual (PDF)

    Abnormal GFCI 150mA

    Likely cause
    The input insulation impedance to the ground decreases while the inverter is working.
    What to do
    If the problem persists, check whether the impedance between the PV string and PE is too low.
  • 15warning
    Manual (PDF)

    Abnormal GFCI

    Likely cause
    The input insulation impedance to the ground decreases while the inverter is working.
    What to do
    If the problem persists, check whether the impedance between the PV string and PE is too low.
  • 18warning
    Manual (PDF)

    Low Insulation Res. (Earth Fault Alarm)

    Likely cause
    The PV string is short-circuited to PE.
    What to do
    Check whether the resistance of the PV string to PE exceeds 50kΩ. If not, check the short circuit point.
  • 19warning
    Manual (PDF)

    Abnormal Ground

    Likely cause
    The PE cable of the inverter is not connected well.
    What to do
    Check whether the PE cable of the inverter is connected properly.
  • 20warning
    Manual (PDF)

    Anti Reverse current protection for hardware

    Likely cause
    Abnormal fluctuation of load.
    What to do
    If the problem occurs frequently and the PV station cannot work properly, contact the dealer or after-sales service.
  • 21warningCall your installer
    Manual (PDF)

    Internal Comm Loss

    Likely cause
    Frame format error, Parity checking error.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 22warningCall your installer
    Manual (PDF)

    AC HCT Check abnormal

    Likely cause
    The sampling of the AC HCT is abnormal.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 23warningCall your installer
    Manual (PDF)

    GFCI HCT Check abnormal

    Likely cause
    The sampling of the GFCI HCT is abnormal.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 27warning
    Manual (PDF)

    DC Arc Fault

    Likely cause
    The DC terminal is not firmly connected.
    What to do
    Read the Quick Installation Guide and check whether the cables are connected properly.
  • 28warningCall your installer
    Manual (PDF)

    AFCI Self-check Fault

    Likely cause
    AFCI detection is abnormal.
    What to do
    Disconnect the AC output switch and DC input switch, then connect them after 5 minutes. Contact the dealer or after-sales service if the problem persists.
  • 9warning
    Manual (PDF)

    Anti-islanding

    Likely cause
    The utility grid is disconnected according to the safety regulations, but the grid voltage is maintained due to loads.
    What to do
    Check whether the utility grid is disconnected. If the problem persists, contact the dealer or after-sales service.
  • 34info
    Manual (PDF)

    String1 PV String Reversed

    Likely cause
    The PV string is connected reversely.
    What to do
    Check whether the PV1 and PV2 strings are connected reversely.
  • 35info
    Manual (PDF)

    String2 PV String Reversed

    Likely cause
    The PV string is connected reversely.
    What to do
    Check whether the PV1 and PV2 strings are connected reversely.

More GoodWe Technologies Co Ltd inverters

GW3600-ES-20 (AS4777-2 2020)

3.68 kW · 1φ

GW3600M-ES-20 (AS4777-2 2020)

3.68 kW · 1φ

GW3600S-BP (AS4777-2 2020)

3.68 kW · 1φ

GW3648C-ES (AS4777-2 2020)

3.68 kW · 1φ

GW3648D-ES (AS4777-2 2020)

3.68 kW · 1φ

GEP3.6-1-10 (AS4777-2 2020)

3.6 kW · 1φ

View all GoodWe Technologies Co Ltd inverters

More from GoodWe

Other CEC-approved products from GoodWe available in Australia.

GoodWe Batteries

GW100KWH-D-10

100.8 kWh · LFP

GW102.4-BAT-AC-G10

100 kWh · LFP

GW112.6-BAT-AC-G10

110 kWh · LFP

GW5.1-BAT-D-G20

5 kWh · LFP

GW5.1-BAT-D-G21

5 kWh · LFP

GW6.0-BAT-D-G20

5.9 kWh · LFP

View all GoodWe batteries

GoodWe Solar Panels

BMM-T3/108A(505W)

505W

BMM-T3/108A(510W)

510W

BMM-T3/108A(515W)

515W

BMM-T3/120A(565W)

565W

BMM-T3/120A(570W)

570W

BMM-T3/120A(575W)

575W

View all GoodWe panels
View full GoodWe manufacturer profile

Want to take the next step?

Get a quote from a member installer who covers your area. You choose whether to act on it. No obligation.

We collect these details to prepare your quote match and to share with the installer(s) we match you with. Not providing them means we can't match you. Full collection notice.

Or explore your battery options first →

By requesting quotes you agree to be contacted by installers in our network about your enquiry. Part of WattMate Pty Ltd. No spam, opt out any time.

About this data

All inverter specifications are sourced from the CEC Approved Products Register. Specifications are provided as published by the CEC and may differ from manufacturer datasheets. Verify current specifications with the manufacturer or your installer before purchasing. Not all listed models may be currently available in Western Australia.

Explore your optionsCompare inverters
Spotted something outdated?