Skip to main content
Solar Battery PerthSolar Battery Perth
  • Library
  • Compare
  • Calculate savings
  • Quote
  • Tools
Battery matcher
Battery matcher

Rebate and policy updates by email

What's changing with WA rebates and battery rules, for Perth homeowners.

Solar Battery Perth

WA-specific solar and battery tools with transparent installer matching for Synergy and Western Power customers.

  • 08 9429 8803
  • info@solarbatteryperth.com.au
Explore your optionsCompare products

Tools

  • Solar system quiz
  • Side-by-side comparison
  • Savings calculator
  • Tariff comparison
  • VPP earnings
  • Quote evaluator
  • Warranty comparison
  • Library
  • Product search
  • All tools

Information

  • How it works
  • Resources
  • WA rebates & incentives
  • Battery price index
  • Synergy tariffs
  • Financing
  • Getting started
  • Buyer's guide
  • Solar and battery integration
  • Battery scenarios

Get started

  • Find installers
  • Perth suburbs
  • Brands
  • Contact us
  • Common questions
Privacy policyTerms of useDisclaimerReview policyAffiliate disclosureAccessibility

© 2026 Solar Battery Perth, operated by WattMate Pty Ltd. Independent solar and battery resource for WA homeowners.

Installers pay us a flat $30 including GST per accepted lead, the same for every installer and every system. How it works

45 Ventnor Avenue, West Perth WA 6005

  • Home
  • Library
  • Compare
  • Savings
  • Quote
  1. Home
  2. Inverters
  3. Sungrow
  4. Residential series
  5. SG2K5-S-NI

Solar inverter · Sungrow · Residential series · CEC approval expired

Sungrow SG2K5-S-NI

CEC listing: SG2K5-S-NI (AS4777-2 2020)

A 2.5 kW single-phase solar inverter.

Rated power
2.5kWHow much solar it can run at once
Battery-ready
NoSolar-only: a battery later means a hybrid swap or a second inverter

Get this inverter quoted in Perth

Enter your postcode and get a free, no-obligation quote from a member installer who covers your area.

SG2K5-S-NI: the short answer

In the Residential seriesThe 2nd of 9 sizes, from 2 to 25 kW
2.5kWThe 2nd of 9 sizes, from 2 to 25 kW
Feed-in credits (DEBS)DEBS pays for exports only when the inverter is 5 kW or less
YesDEBS pays for exports only when the inverter is 5 kW or less

Other sizes in the Residential series

  • 2 kW
  • 2.5 kW (this one)
  • 3 kW
  • 5 kW
  • 8 kW
  • 10 kW
  • 15 kW
  • 20 kW
  • 25 kW

What we can tell you

Read from the figures on this page. No review written yet.

  • It is a solar-only inverter: adding a battery later means replacing it with a hybrid inverter, or keeping it and adding an AC-coupled battery, which in WA counts as an alteration with whole-of-site compliance.
  • It runs on a standard single-phase supply.
  • Its CEC approval has expired, so a new install with it wouldn't qualify for STCs.
  • We hold no captured datasheet for this model yet, so the specs below come from the CEC register only.

Key specs, in plain terms

The numbers that matter for a home. The full datasheet is below.

Rated power
2.5kW
How much solar it can turn into usable power at once
Phases
Single
Runs on a standard single-phase supply
Type
Solar
Runs solar only

Full datasheet

Every figure on file for the Sungrow SG2K5-S-NI, by section.

Full datasheet, by section
SpecificationValue
Power & output
Nominal power8 kW
Efficiency
Max efficiency97.8%
European efficiency97.3%
Physical
Weight19 kg
IP ratingIP65
Installation requirements
Top clearance500 mm
Side clearance300 mm
AC breaker50 A
Cable gauge6 mm²
Earthing methodTN-S
DNSP pre-approvalYes
Estimated install time8 hrs

Parsed from the manufacturer datasheet, install manual, and warranty document. Confirm against the linked PDFs before relying on a value for a quote or installation.

Features and CEC approval

Battery compatible
No
Backup capable
No
CEC approved
28 June 2022
Approval expiry
28 June 2025
Status
Not listed
Listed for STCs
No (not listed)

About Sungrow

Years on the CEC list
5 years
Australian office
Yes
Category
Premium
CEC-approved inverters
50
CEC-approved batteries
19
CEC-approved panels
145
View full profile →
Explore your options

Get a quote from an installer sourced from the WA (Synergy/Plenti) approved list

  • Compare with other inverters→
  • Already have a quote? Check it→
  • Sungrow batteries and panels→

WA compliance

ESM compliant
Check

Western Power approval is required for every grid-connected install. Under Emergency Solar Management, a new system must be remotely manageable, or take an export limit instead. Ask your installer to confirm this inverter’s ESM status.

Perth performance

Estimate for a full-size array on this inverter

Daily yield
10.6 kWh
Annual yield
3,878 kWh

At 5 peak sun hours a day (BOM) with a 15% system derate.

Australian office

Has local presence

Website

www.sungrowpower.com/au/en
5 years on the CEC list

How it compares

The Sungrow SG2K5-S-NI against the closest-power inverters from other brands.

Specification
Sungrow SG2K5-S-NISungrow
Afore AF2.5K-SL-1Afore
Enphase IQBATTERY-5P-3P-INT-2.50-1PEnphase
Rated power?2.5 kW2.5 kW2.5 kW
Max efficiency?Not on fileNot on fileNot on file
MPPT trackers?Not on fileNot on fileNot on file
PhasesSingle-phaseSingle-phaseSingle-phase
TypeSolarHybridSolar
Battery readyNoYesNo
WarrantyNot on fileNot on fileNot on file

Specs from the CEC register and datasheet enrichment. Indicative: confirm exact figures with your installer.

Documents

  • Warranty termsPDF, opens in a new tab

Warranty summary

Sungrow offers a 10-year warranty on inverters, covering defects in materials and workmanship. Unauthorized modifications void coverage. To make a claim, contact your installer for troubleshooting and submit a warranty claim online.

10-year inverter warranty

Sungrow SG2K5-S-NI

Sungrow offers a 10-year warranty on inverters, covering defects in materials and workmanship. Unauthorized modifications void coverage. To make a claim, contact your installer for troubleshooting and submit a warranty claim online.

AI-summarised from the manufacturer warranty document. Always confirm against the linked PDF before relying on it for a claim.

Coverage shape
Full-replacement coverage
If you sell the home
Transfers to the next homeowner
What voids it
Unauthorized repairs, modifications, improper installation, and failure to follow operating instructions void warranty.
Environment limits
Conditions exceeding the temperature limitations of -20°C to 50°C void coverage.
Read the official warranty document (PDF)

Fault & error codes — Sungrow SG2K5-S-NI

From the install manual

21 documented

Showing 21 of 21. The official install manual is the authoritative source — always confirm before acting.

  • 10criticalCall your installer
    Manual (PDF)

    Grid Power Outage

    Likely cause
    No power supplied from the grid
    What to do
    Check if the grid power supply is reliable. Ensure AC cable connections are firm and the AC circuit breaker is connected.
  • 2criticalCall your installer
    Manual (PDF)

    Grid Overvoltage

    Likely cause
    Local grid voltage high
    What to do
    Wait for grid to return to normal; measure actual grid voltage and contact electric company if needed.
  • 28criticalCall your installer
    Manual (PDF)

    PV Reserve Connection Fault

    Likely cause
    Reverse polarity in string
    What to do
    Disconnect DC switch and adjust polarity when string current drops below 0.5A.
  • 29criticalCall your installer
    Manual (PDF)

    PV Reserve Connection Fault

    Likely cause
    Reverse polarity in string
    What to do
    Disconnect DC switch and adjust polarity when string current drops below 0.5A.
  • 3criticalCall your installer
    Manual (PDF)

    Grid Overvoltage

    Likely cause
    Local grid voltage high
    What to do
    Wait for grid to return to normal; measure actual grid voltage and contact electric company if needed.
  • 4criticalCall your installer
    Manual (PDF)

    Grid Undervoltage

    Likely cause
    Local grid voltage low
    What to do
    Wait for grid to return to normal; measure actual grid voltage and contact electric company if needed.
  • 5criticalCall your installer
    Manual (PDF)

    Grid Undervoltage

    Likely cause
    Local grid voltage low
    What to do
    Wait for grid to return to normal; measure actual grid voltage and contact electric company if needed.
  • 532-547, 564-579criticalCall your installer
    Manual (PDF)

    PV Reverse Connection Alarm

    Likely cause
    Incorrect polarity in PV connections
    What to do
    Disconnect DC switch and adjust the polarity when current drops below 0.5 A.
  • 54criticalCall your installer
    Manual (PDF)

    Electric Arc Fault

    Likely cause
    Damaged DC cable or connection issues
    What to do
    Check connections; replace damaged cables.
  • 12warningCall your installer
    Manual (PDF)

    Excess Leakage Current

    Likely cause
    Moisture or poor insulation
    What to do
    Wait for conditions to improve. Inspect AC and DC cables to ensure they are well insulated.
  • 13warningCall your installer
    Manual (PDF)

    Grid Abnormal

    Likely cause
    Grid parameters exceed acceptable values
    What to do
    Measure grid parameters and contact the local electric power company for solutions if necessary.
  • 17warningCall your installer
    Manual (PDF)

    Grid Voltage Imbalance

    Likely cause
    Voltage difference between phases
    What to do
    Measure actual grid voltages and contact electric company for solutions if needed.
  • 2, 3, 14, 15warningCall your installer
    Manual (PDF)

    Grid Overvoltage

    Likely cause
    An issue with the grid voltage being higher than allowed
    What to do
    Wait for the grid to return to normal. If this occurs repeatedly, measure the actual grid voltage and contact your local electric power company.
  • 37warningCall your installer
    Manual (PDF)

    Excessively High Ambient Temperature

    Likely cause
    Inverter overheated due to high ambient temperature
    What to do
    Wait for the temperature to return to normal. Ensure good ventilation around the inverter.
  • 4, 5warningCall your installer
    Manual (PDF)

    Grid Undervoltage

    Likely cause
    Grid voltage is lower than allowed
    What to do
    Wait for the grid to return to normal. If this occurs repeatedly, measure the actual grid voltage and contact your local electric power company.
  • 43warning
    Manual (PDF)

    Excessively Low Ambient Temperature

    Likely cause
    Inverter is below operational temperature range
    What to do
    Stop and disconnect the inverter. Restart when conditions improve.
  • 48warningCall your installer
    Manual (PDF)

    PV Abnormal Alarm

    Likely cause
    Sheltering or shielding of module
    What to do
    Remove obstruction and ensure module cleanliness.
  • 548-563, 580-595warningCall your installer
    Manual (PDF)

    PV Abnormal Alarm

    Likely cause
    Abnormal voltage or current in PV connections
    What to do
    Inspect PV modules and connection integrity. Check for shading or loose wiring.
  • 8warningCall your installer
    Manual (PDF)

    Grid Overfrequency

    Likely cause
    Grid frequency exceeds the allowed range
    What to do
    Wait for the grid to return to normal. If this occurs repeatedly, measure the actual grid frequency and contact your local electric power company.
  • 84warningCall your installer
    Manual (PDF)

    Reverse Connection Alarm of the Meter/CT

    Likely cause
    Incorrect meter connection
    What to do
    Check and correct meter wiring.
  • 9warningCall your installer
    Manual (PDF)

    Grid Underfrequency

    Likely cause
    Grid frequency is below the allowed range
    What to do
    Wait for the grid to return to normal. If this occurs repeatedly, measure the actual grid frequency and contact your local electric power company.

More Sungrow inverters

SG2K5-S (AS4777-2 2020)

2.5 kW · 1φ

SG2.0RS-S (AS4777-2 2020)

2 kW · 1φ

SG2K-S (AS4777-2 2020)

2 kW · 1φ

SG2K-S-NI (AS4777-2 2020)

2 kW · 1φ

SG3.0RS (AS4777-2 2020)

3 kW · 1φ

SG3K-D (AS4777-2 2020)

3 kW · 1φ

View all Sungrow inverters

More from Sungrow

Other CEC-approved products from Sungrow available in Australia.

Sungrow Batteries

SBH100

10 kWh

SBH150

15 kWh

SBH200

20 kWh

SBH250

25 kWh

SBH300

30 kWh

SBH350

35 kWh

View all Sungrow batteries

Sungrow Solar Panels

SG-48TG2D-470

470W

SG-48TG2D-475

475W

SG-48TG2D-480

480W

SG-48TG2D-X-465

465W

SG-48TG2D-X-470

470W

SG-48TG2D-X-475

475W

View all Sungrow panels
View full Sungrow manufacturer profile

Want to take the next step?

Get a quote from a member installer who covers your area. You choose whether to act on it. No obligation.

We collect these details to prepare your quote match and to share with the installer(s) we match you with. Not providing them means we can't match you. Full collection notice.

Or explore your battery options first →

By requesting quotes you agree to be contacted by installers in our network about your enquiry. Part of WattMate Pty Ltd. No spam, opt out any time.

About this data

All inverter specifications are sourced from the CEC Approved Products Register. Specifications are provided as published by the CEC and may differ from manufacturer datasheets. Verify current specifications with the manufacturer or your installer before purchasing. Not all listed models may be currently available in Western Australia.