Skip to main content
Solar Battery PerthSolar Battery Perth
  • Library
  • Compare
  • Calculate savings
  • Quote
  • Tools
Battery matcher
Battery matcher

Rebate and policy updates by email

What's changing with WA rebates and battery rules, for Perth homeowners.

Solar Battery Perth

WA-specific solar and battery tools with transparent installer matching for Synergy and Western Power customers.

  • 08 9429 8803
  • info@solarbatteryperth.com.au
Explore your optionsCompare products

Tools

  • Solar system quiz
  • Side-by-side comparison
  • Savings calculator
  • Tariff comparison
  • VPP earnings
  • Quote evaluator
  • Warranty comparison
  • Library
  • Product search
  • All tools

Information

  • How it works
  • Resources
  • WA rebates & incentives
  • Battery price index
  • Synergy tariffs
  • Financing
  • Getting started
  • Buyer's guide
  • Solar and battery integration
  • Battery scenarios

Get started

  • Find installers
  • Perth suburbs
  • Brands
  • Contact us
  • Common questions
Privacy policyTerms of useDisclaimerReview policyAffiliate disclosureAccessibility

© 2026 Solar Battery Perth, operated by WattMate Pty Ltd. Independent solar and battery resource for WA homeowners.

Installers pay us a flat $30 including GST per accepted lead, the same for every installer and every system. How it works

45 Ventnor Avenue, West Perth WA 6005

  • Home
  • Library
  • Compare
  • Savings
  • Quote
  1. Home
  2. Inverters
  3. Hoymiles
  4. HMS-2000-4T

Solar inverter · Hoymiles · CEC approved September 2024

Hoymiles HMS-2000-4T

CEC listing: HMS-2000-4T (AS4777-2 2020)

A 2 kW single-phase solar inverter.

Rated power
2kWHow much solar it can run at once
Battery-ready
NoSolar-only: a battery later means a hybrid swap or a second inverter
Datasheet (PDF)

Get this inverter quoted in Perth

Enter your postcode and get a free, no-obligation quote from a member installer who covers your area.

HMS-2000-4T: the short answer

Feed-in credits (DEBS)DEBS pays for exports only when the inverter is 5 kW or less
YesDEBS pays for exports only when the inverter is 5 kW or less

Is it right for your home?, Hoymiles HMS-2000-4T

Hoymiles HMS microinverters convert power at the panel, with one unit serving two or four panels depending on the model. Each panel is tracked on its own, so shade on one has less effect on the rest.

Where a Perth roof has shade, or panels facing different ways, HMS gives that per-panel layout. It is rapid shutdown capable, and monitoring runs through the S-Miles app.

What it does well

  • Per-panel optimisation
  • Better partial-shade handling than a string inverter
  • One unit covers two or four panels

Where it falls short

  • 12-year warranty (Enphase IQ8 is 25 years)
  • DTU gateway needed for export limiting

A good fit for

  • Roofs with panels facing different ways
  • Shaded roofs

Key specs, in plain terms

The numbers that matter for a home. The full datasheet is below.

Rated power
2kW
How much solar it can turn into usable power at once
Max efficiency
96.5%
How much of the solar you make reaches the house
Phases
Single
Runs on a standard single-phase supply
MPPT trackers
4
4 roof faces can be tuned independently
Type
Solar
Runs solar only
Warranty
25yr
How long Hoymiles Power Electronics Inc stands behind it

Full datasheet

Every figure on file for the Hoymiles HMS-2000-4T, by section.

Full datasheet, by section
SpecificationValue
Power & output
Nominal power2 kW
Maximum power2 kW
Apparent power2 kVA
Phases1
Efficiency
Max efficiency96.5%
European efficiency99.8%
CEC-weighted efficiency99.8%
DC input & MPPT
MPPT trackers4
Max input voltage65 V
MPPT voltage min16 V
MPPT voltage max60 V
Max input current64 A
Battery & backup
Battery compatibleNo
Backup capableNo
Continuous backup9.09 kW
Physical
Dimensions (H×W×D)218 × 331 × 35 mm
Weight4.7 kg
IP ratingIP67
CoolingNatural convection
Operating temperature-40°C to 65°C

Parsed from the manufacturer datasheet, install manual, and warranty document. Confirm against the linked PDFs before relying on a value for a quote or installation.

Features and CEC approval

Battery compatible
No
Backup capable
No
CEC approved
2 Sept 2024
Approval expiry
2 Sept 2027
Status
Active
Listed for STCs
Yes

About Hoymiles

Years on the CEC list
7 years
Australian office
Yes
Category
Mid-Tier
CEC-approved inverters
68
CEC-approved batteries
32
View full profile →
Explore your options

Get a quote from an installer sourced from the WA (Synergy/Plenti) approved list

  • Compare with other inverters→
  • Already have a quote? Check it→

WA compliance

ESM compliant
Check

Western Power approval is required for every grid-connected install. Under Emergency Solar Management, a new system must be remotely manageable, or take an export limit instead. Ask your installer to confirm this inverter’s ESM status.

Perth performance

Estimate for a full-size array on this inverter

Daily yield
8.5 kWh
Annual yield
3,103 kWh

At 5 peak sun hours a day (BOM) with a 15% system derate.

Australian office

Has local presence

Website

www.hoymiles.com/au
7 years on the CEC list

How it compares

The Hoymiles HMS-2000-4T against the closest-power inverters from other brands.

Specification
Hoymiles HMS-2000-4THoymiles
Altenergy Power System DS3D-HAltenergy Power System
Altenergy Power System DS3D-HAltenergy Power System
Rated power?2 kW2 kW2 kW
Max efficiency?96.5%Not on fileNot on file
MPPT trackers?4Not on fileNot on file
PhasesSingle-phaseSingle-phaseSingle-phase
TypeSolarSolarSolar
Battery readyNoNoNo
Warranty25 yearsNot on fileNot on file

Specs from the CEC register and datasheet enrichment. Indicative: confirm exact figures with your installer.

Documents

  • DatasheetPDF, opens in a new tab
  • Warranty termsPDF, opens in a new tab
  • Installation guide and user manualPDF, opens in a new tab
  • Compliance certificatePDF, opens in a new tab

25-year inverter warranty

Hoymiles HMS-2000-4T

Hoymiles offers a warranty that covers defects in manufacturing for different products ranging from 3 to 25 years. Exclusions include improper installations and environmental damage, and claims must be initiated through a qualified installer.

AI-summarised from the manufacturer warranty document. Always confirm against the linked PDF before relying on it for a claim.

Coverage shape
Full-replacement coverage
If you sell the home
Transfers to the next homeowner
What voids it
Improper or non-compliant use; improper installation; damage during transportation; unauthorized repair attempts; products purchased from unauthorized dealers.
Environment limits
Installation in a corrosive environment.
Read the official warranty document (PDF)

Fault & error codes — Hoymiles HMS-2000-4T

From the install manual

34 documented

Showing 34 of 34. The official install manual is the authoritative source — always confirm before acting.

  • 147criticalCall your installer
    Manual (PDF)

    Power grid outage

    Likely cause
    Grid connection issue.
    What to do
    Check AC switch, branch breaker, and AC wiring.
  • 148criticalCall your installer
    Manual (PDF)

    Grid disconnection

    Likely cause
    Issue with AC connection.
    What to do
    Check AC switch, branch breaker, and AC wiring.
  • 209criticalCall your installer
    Manual (PDF)

    No input

    Likely cause
    PV module not connected.
    What to do
    Confirm connection of this port to the PV module. Check DC cable connection if already connected.
  • 210criticalCall your installer
    Manual (PDF)

    No input

    Likely cause
    PV module not connected.
    What to do
    Confirm connection of this port to the PV module. Check DC cable connection if already connected.
  • 211criticalCall your installer
    Manual (PDF)

    No input

    Likely cause
    PV module not connected.
    What to do
    Confirm connection of this port to the PV module. Check DC cable connection if already connected.
  • 212criticalCall your installer
    Manual (PDF)

    No input

    Likely cause
    PV module not connected.
    What to do
    Confirm connection of this port to the PV module. Check DC cable connection if already connected.
  • 121warning
    Manual (PDF)

    Over temperature protection

    Likely cause
    Ventilation and ambient temperature issues at the installation location.
    What to do
    Improve ventilation and heat dissipation. Contact your dealer if issues persist.
  • 124warning
    Manual (PDF)

    Shut down by remote control

    Likely cause
    Status of zero export management or manual shutdown.
    What to do
    Check the status of zero export management and whether the microinverters were manually shut down. Contact your dealer if the issue persists.
  • 125warningCall your installer
    Manual (PDF)

    Grid configuration parameter error

    Likely cause
    Incorrect grid configuration parameters.
    What to do
    Check grid configuration parameters and upgrade. Contact your dealer if the fault persists.
  • 127warningCall your installer
    Manual (PDF)

    Firmware error

    Likely cause
    Incorrect or outdated firmware.
    What to do
    Check if the firmware is correct and upgraded. Check communication with DTU. Contact your dealer if the issue persists.
  • 130warningCall your installer
    Manual (PDF)

    Offline

    Likely cause
    Microinverter not functioning correctly.
    What to do
    Check DC voltage range and LED indicator status. Check communication with DTU. Contact your dealer if issues persist.
  • 141warningCall your installer
    Manual (PDF)

    Grid overvoltage

    Likely cause
    Occasional temporary grid voltage abnormality.
    What to do
    Monitor grid voltage. Contact local power operator if frequent.
  • 142warningCall your installer
    Manual (PDF)

    10 min value grid overvoltage

    Likely cause
    Temporary grid overvoltage.
    What to do
    Monitor the grid voltage. Contact local power operator if frequent.
  • 143warningCall your installer
    Manual (PDF)

    Grid undervoltage

    Likely cause
    Occasional temporary low grid voltage.
    What to do
    Monitor grid voltage. Contact local power operator if frequent.
  • 144warningCall your installer
    Manual (PDF)

    Grid overfrequency

    Likely cause
    Temporary high grid frequency.
    What to do
    Monitor grid frequency. Contact local power operator if frequent.
  • 145warningCall your installer
    Manual (PDF)

    Grid underfrequency

    Likely cause
    Temporary low grid frequency.
    What to do
    Monitor grid frequency. Contact local power operator if frequent.
  • 146warningCall your installer
    Manual (PDF)

    Rapid grid frequency change rate

    Likely cause
    Occasional rapid frequency change in grid.
    What to do
    Monitor grid frequency change rate. Contact local power operator if frequent.
  • 149warningCall your installer
    Manual (PDF)

    Island detected

    Likely cause
    Temporary islanding condition.
    What to do
    Check with local power operator if alarms occur frequently. Contact dealer if issue persists.
  • 205warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    PV module open-circuit voltage exceeds maximum input voltage.
    What to do
    Ensure PV module voltage is within the maximum input voltage. Contact your dealer if it is.
  • 206warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    PV module open-circuit voltage exceeds maximum input voltage.
    What to do
    Ensure PV module voltage is within the maximum input voltage. Contact your dealer if it is.
  • 207warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    PV module voltage is below minimum input voltage.
    What to do
    Ensure PV module voltage is not lower than minimum input voltage. Contact your dealer if it is.
  • 208warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    PV module voltage is below minimum input voltage.
    What to do
    Ensure PV module voltage is not lower than minimum input voltage. Contact your dealer if it is.
  • 213warningCall your installer
    Manual (PDF)

    PV-1 & PV-2 abnormal wiring

    Likely cause
    Incorrect connection on ports 1 and 2.
    What to do
    Check DC connections on port 1 and 2. Verify DC extension cable.
  • 214warningCall your installer
    Manual (PDF)

    PV-3 & PV-4 abnormal wiring

    Likely cause
    Incorrect connection on ports 3 and 4.
    What to do
    Check DC connections on port 3 and 4. Verify DC extension cable.
  • 215warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    Input voltage higher than allowable for PV-1.
    What to do
    Check input voltage of PV-1 port.
  • 216warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    Input voltage lower than allowable for PV-1.
    What to do
    Check input voltage of PV-1 port.
  • 217warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    Input voltage higher than allowable for PV-2.
    What to do
    Check input voltage of PV-2 port.
  • 218warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    Input voltage lower than allowable for PV-2.
    What to do
    Check input voltage of PV-2 port.
  • 219warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    Input voltage higher than allowable for PV-3.
    What to do
    Check input voltage of PV-3 port.
  • 220warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    Input voltage lower than allowable for PV-3.
    What to do
    Check input voltage of PV-3 port.
  • 221warningCall your installer
    Manual (PDF)

    Input overvoltage

    Likely cause
    Input voltage higher than allowable for PV-4.
    What to do
    Check input voltage of PV-4 port.
  • 222warningCall your installer
    Manual (PDF)

    Input undervoltage

    Likely cause
    Input voltage lower than allowable for PV-4.
    What to do
    Check input voltage of PV-4 port.
  • 301-314warningCall your installer
    Manual (PDF)

    Device failure

    Likely cause
    Occasional failure not affecting normal operation.
    What to do
    No special treatment required if occasional. Contact your dealer if frequent.
  • 129info
    Manual (PDF)

    Abnormal bias

    Likely cause
    Occasional occurrence of alarm without affecting functionality.
    What to do
    No special treatment required if occasional. Contact your dealer if frequent and cannot be recovered.

More Hoymiles Power Electronics Inc inverters

HMS-2000C-4T (AS4777-2 2020)

2 kW · 1φ

HMS-1800-4T (AS4777-2 2020)

1.8 kW · 1φ

HMS-1800C-4T (AS4777-2 2020)

1.8 kW · 1φ

HMS-1600-4T (AS4777-2 2020)

1.6 kW · 1φ

HMS-1600C-4T (AS4777-2 2020)

1.6 kW · 1φ

HME-1500-AU (AS4777-2 2020)

1.5 kW · 1φ

View all Hoymiles Power Electronics Inc inverters

More from Hoymiles

Other CEC-approved products from Hoymiles available in Australia.

Hoymiles Batteries

HBX-10LV-G1

9.21 kWh · LFP

HBX-5LV-G1

4.6 kWh · LFP

HiOne-10S-16B-G3-AU (AS4777-2 2020)

15.6 kWh · LFP

HiOne-10S-24B-G3-AU (AS4777-2 2020)

23.4 kWh · LFP

HiOne-10S-32B-G3-AU (AS4777-2 2020)

31.2 kWh · LFP

HiOne-10T-16B-G3-AU (AS4777-2 2020)

15.6 kWh · LFP

View all Hoymiles batteries
View full Hoymiles manufacturer profile

Want to take the next step?

Get a quote from a member installer who covers your area. You choose whether to act on it. No obligation.

We collect these details to prepare your quote match and to share with the installer(s) we match you with. Not providing them means we can't match you. Full collection notice.

Or explore your battery options first →

By requesting quotes you agree to be contacted by installers in our network about your enquiry. Part of WattMate Pty Ltd. No spam, opt out any time.

About this data

All inverter specifications are sourced from the CEC Approved Products Register. Specifications are provided as published by the CEC and may differ from manufacturer datasheets. Verify current specifications with the manufacturer or your installer before purchasing. Not all listed models may be currently available in Western Australia.

Explore your optionsCompare inverters
Spotted something outdated?